01
Inspect
A documented, risk-based inspection and maintenance programme for communal containment.
Site Voyance Ltd · Consultation draft v0.3
Shared electrical containment
Version 0.3 · 7 November 2026
Meter cupboards and risers often hold equipment for more than one flat, supplier and contractor. A defect in that shared space can harm the next worker and, where the cupboard is reachable, residents. Isolating one meter does not make the trunking dead.
This framework makes existing safety duties easier to apply at the joins between the building network operator, the building owner, suppliers, metering organisations and residents. It does not create a new universal legal duty, and it does not claim a statutory communal electrical MOT.
01
A documented, risk-based inspection and maintenance programme for communal containment.
02
A Shared Containment Disturbance Assessment inside the metering work risk assessment.
03
A consistent continue, control, or stop-and-escalate decision, including protection of residents.
04
A named dutyholder, normally the BNO where the containment is BNO-controlled, without owning every cable.
05
Competent contractors may tender for planned repair. Urgent danger is controlled before tendering.
06
A justified Infrastructure Safety Abort is kept out of avoidable-failure metrics. Cost recovery is a separate contract question.
The consultation document itself, not a summary. Read it here. Download any file. These links stay on the published app.



















Several meters may sit in one trunking or riser, for different suppliers, with different cable owners and a history of covers being removed and refitted. The visiting engineer can assess the task. That point-of-work assessment does not replace the infrastructure controller’s inspection and defect programme, and the engineer is not there to repair another flat’s cables under a meter-exchange order.
If the engineer stops, the visit can be recorded as a failure, and the defect can pass between managers with no common reference and no confirmed close-out. The next engineer, or a resident, then meets the same condition.
Shared infrastructure needs an identifiable controller. Everyone working on or near it still owns the safety of their own activity.
Gloves are not a substitute for controlling the hazard. A damaged cover must not be refixed with a convenient long screw without knowing what is behind it. Single-insulated conductors are not unsafe merely because they are inside suitable, fully enclosed containment. The concern is damaged insulation, a failed enclosure, or unsafe access.
Electricity at Work Regulations 1989, especially the duties on construction, maintenance, mechanical damage, insulation, and work on or near live conductors. The Management of Health and Safety at Work Regulations 1999 require a suitable assessment of risks to employees and to other people. The Health and Safety at Work etc. Act 1974 extends duties, so far as reasonably practicable, to people outside the employment, which matters where residents can reach a cupboard.
UK Power Networks’ BNO guidance describes design, installation, maintenance and safety responsibilities for the building network. ENA EREC G87 and G104 are relevant to multiple-occupancy connections and to legacy rising and lateral mains, and still need to be read against the actual building. England’s rented-sector five-year checks do not apply to communal areas under those rules, which is not a reason to leave a shared system uninspected.
Nothing reviewed here creates a universal duty for every BNO to pay for every third-party meter tail, or an automatic liability for a supplier’s failed-visit charge.
An asset register, a baseline look at older installations, intervals set by condition and consequence, extra inspection after damage or repeated aborts, a defect register, and planned refurbishment where local repairs will not hold. No annual or five-year interval is claimed as existing law.
Before work that could disturb shared containment, record the foreseeable interface with neighbouring circuits. The assessment does not certify the block. If an adjacent circuit cannot be identified or isolated as needed, or the work could move damaged live conductors, do not proceed without further authority.
A training aid, not a permit. Answer only what you can see without creating danger. Unknown is not a No. The result is calculated from what you record. You cannot mark the task as clear while a stop answer is recorded.
Pictures are offered only on questions about something you can see: the cover, fixings, damage, congestion, edges, metalwork, the place, and whether residents can reach it. They are not asked for isolation authority, a missing controller, or whether the task will move a tail. Do not open a hazard to take one.
This is a training and consultation exercise, not a work permit. Until you upload, pictures stay in this browser only. Upload stores the report and its pictures in this app’s private consultation store, under your sign-in. They are not emailed, and nobody else is given a list of them. Feedback goes to that same store, not to an address, because this draft publishes none.
1. Cover missing, loose, bent, damaged or inadequately secured?
2. Fasteners or penetrations could damage enclosed cables?
3. Exposed copper, damaged insulation or makeshift repairs?
4. Unprotected edges or signs of abrasion?
5. Congestion likely to move other circuits?
6. Non-sheathed conductors could be exposed if the enclosure is disturbed?
7. Adjacent conductors may stay live and be affected?
8. Circuit identity, isolation boundary or authority unclear?
9. Concern about accessible metalwork?
10. Working space, access or lighting inadequate?
11. Water, heat or other environmental damage?
12. Residents can reach a potentially hazardous area?
13. The cover cannot be refitted without undue force?
14. No responsible controller or emergency contact?
15. The task moves shared containment or tails?
Assessment incomplete — 0 of 15 questions answered.
Yes 0. Unknown 0. Counted separately from completion. A low count is not a clearance.
Resident access, not one of the 15: not answered.
Calculated result
Assessment incomplete — 0 of 15 questions answered.
Ownership, operational control, safety coordination and cost liability may be four different answers. Do not infer ownership from cable colour or the branding on a nearby meter.
A metering visit reasonably suspended because communal infrastructure outside the contractor’s authorised task prevents safe work. It is an administrative outcome, not a finding of legal liability.
Pilot governance and reporting in a few buildings with known owners. Do not pilot exposure to danger. Useful signs: faster acknowledgement, interim control before ownership is argued, closures that carry evidence, and fewer later visits finding the same unresolved hazard. A request that someone re-enter a hazard only to finish the form is a failure of the pilot, whatever the other numbers say.
Still unread clause by clause: full CoMCoP, the relevant parts of BS 7671, ENA G87 Issue 3 and G104 Issue 1, distribution licences, connection agreements, and the leases and contracts for the building. 7 November 2026.
No confirmed contact address is published in this draft, so a comment is not emailed. Submit feedback uploads it to this app’s private consultation store, under your sign-in, and names version 0.3 and the section you reviewed. There is no deadline on this page.